Design of Lightning Protection System on Village Hall Building in Residential Area Using Rolling Sphere Method Based on Air Terminal Height Variations
Keywords:
Lightning protection, Rolling sphere, Air terminal, Franklin rodAbstract
This study evaluates the design of a lightning protection system for a residential village hall using the rolling sphere method per IEC 62305 standards. Quantitative engineering calculations were conducted to assess the protection coverage of a Franklin rod air terminal installed on a 5-m-high structure across three height variations: 1 m, 1.5 m, and 2 m. The results demonstrate a direct correlation between air terminal height and protection coverage. Increasing the terminal height from 1 m to 1.5 m and 2 m expanded the protection radius from 21.93 m (1,510 m²) to 23.30 m (1,705 m²) and 24.66 m (1,910 m²), respectively. Technical and economic trade-off analyses identify the 1.5-m Franklin rod as the optimal configuration, delivering effective structural protection while maintaining construction feasibility and cost efficiency. These findings provide a practical benchmark for designing lightning protection systems in small-scale public infrastructure within residential areas.